Calculations
- LIGHT BEAM CALCULATIONS
- Beam diameter = distance * (2 * tan (beam angle / 2))
- Throw distance = Square root ((horizontal dist. * horizontal dist.) + (vertical dist. * vertical dist.))
- LIGHT OUTPUT CALCULATIONS
- 1 candela = 12.57 Lumens
- Foot-candles = candela / distance in feet * distance in feet
- Foot-candles * 10.764 = Lumens/sq meter
- 1 Lumen/sq meter = 1 Lux
- Lumens/sq ft * 1 = foot-candles
- Lumens/sq ft * 10.764 = lumens/sq meter
- Lumens * 0.07958 = spherical candle power
- Lambert * 0.3183 = candles/sq cm
- Lambert * 295.720 = candles sq ft
- Lambert * 1 = lumens/sq cm
- Lumens/sq. ft. * 1 = foot-candles
- Lumens/sq. ft. * 10.764 = lumens/sq meter
- Lumens * 0.07958 = spherical candle power
- Lux = candela / distance in meters * distance in meters
- Lux * 0.0929 = foot-candles
- LUMINAIRES EFFICIENCY RATING - LER
- EFF = luminaire efficiency
- TLL = total number of lamps per luminaire X rated lumens per lamp
- BF= ballast factor
- IW = Input Watts, the total system watts of the luminaire
- LER = EFF X TLL x BF / IW
- POWER CALCULATIONS
- Power = Voltage * current (Watts = Volts * Amps)
- Current = Power / Voltage (Amps = Watts / Volts)
- RMS Volts = 0.707 * Peak Volts RMS Volts = 1.11 * Average Volts
- ROOM CAVITY RATIO
- RCR = 5 * H * (L+W) / (L * W)
- RCR = 2.5 * Total Wall Area / Floor Area
- H = height
- L = length
- W = width of the room
- A cubical room will have an RCR of 10, the flatter the room the lower the RCR.
- SPACING TO MOUNTING HEIGHT RATIO
- Sp = Spacing between Lights
- MH = Mounting Height above Work Area (living room floor, or kitchen countertop)
- WH = Wall Height
- DfW = Distance from Wall
- DtO = Distance to Object
- Recessed Downlighting with Incandescent Flood Light Bulbs
- Sp = 3/4 * MH to a maximum of 1 * MH
- Recessed Downlighting with Halogen Flood Lights
- Sp = 1/2 * MH to a maximum of 3/4 * MH
- Wallwashing with Recessed, Track, or Landscaping Lights
- Sp = 1/4 * WH,
- DfW = 1/4 * WH, and
- Aim 1/4 down the wall, or up the wall in the case of landscape lights
- Grazing with Recessed, Track, or Landscaping Lights
- Sp = 12 - 18",
- DfW = 6 - 12"
- Highlighting Paintings with Recessed, or Track Lights
- DfW = 2/3 * DtO
- Highlighting Three Dimensional Pieces with Recessed, Track, or Landscaping Lights
- DfW = 2/3 * DtO
- Sp = 12 - 18"
- VOLTAGE DROP OF CONDUCTOR - LENGTH CALCULATION
- V = voltage drop,
- I = current
- L = length of conductor in feet
- R = resistance of conductor per 1000 feet
- R for 18awg = 6.51, 16awg = 4.09, 14awg = 2.58, 12awg = 1.62, 10awg = 1.02, 8awg = 0.64
- V = I * L * (R / 1000) * 1.004
|
|
|